Sign In
Non-maloperate Testing
Product Code: NA
Type tests are facilitated at Cranage for Substation Equipment and Transducer Based Monitoring Systems for Power Cables:- operating on AC/DC power supplies, including:-
BS EN61000-4-2 (contact/air discharge up to ±15kV)
BS EN61000-4-3 (up to 30V/m including 10V/m at 0.9/1.89GHz)
BS EN61000-4-4 (up to ±4kV)
BS EN61000-4-5 (up to ±4kV)
BS EN61000-4-6 (up to 10V rms)
BS EN61000-4-8 (up to 100A/m)
BS EN61000-4-9 (up to 1000A/m)
BS EN61000-4-10 (up to 100A/m)
BS EN61000-4-11 (AC/DC interruptions + voltage variations)
BS EN61000-4-12 (see below)
BS EN61000-4-16 (15Hz to 150kHz up to 10V rms including 30/300V 50Hz test)
BS EN55022 (emissions Class A & B limits on 10m open area test site)
IEC 255-5 (500V/2000V dielectric test)
Damped Oscillatory Wave tests have been developed at Cranage in co-operation with the National Grid Company plc.
Pulsed and Damped Oscillatory Magnetic Field tests are also facilitated at Cranage to meet the requirements of BS EN61000-4-9 (up to 1000A/m) and BS EN61000-4-10 (up to 100A/m).
BS EN61000-4-12: Damped Oscillatory Wave
These tests are intended to simulate the effects of switching with restrike of the arc, e.g. disconnector operation and are applied on cables used for cross site connections of analogue signals, including HV and telecomms equipment. AC and DC supply inputs are also included.
Calibrated equipment at Cranage comprises an Oscillatory Wave Generator and Four-line Coupling network rated up to 25A per phase with the following specifications:-
Technical Data: Generator
Sinusoidal amplitude 200 to 3000V (off load) - up to 2.5kV on four line network load
Polarity positive / negative / alternating
Burst frequency 100kHz / 1MHz +10%
Burst repetition 2/s to 50/s (40/s for 100kHz burst frequency)
2/s to 500/s (400/s for 1MHz burst frequency)
Test duration 1s to 29999s (2s minimum for BS EN61000-4-12)
Generator impedance 200W
Triggering single burst / asynchronous / synchronous
Sync frequencies 40Hz / 50Hz / 60Hz / 400Hz / 16.6Hz
Sync angle 0 to 360 degrees
Technical Data: Coupling Network
AC Voltage range 420V phase-phase
240V phase-neutral
240V phase-earth
DC Voltage range 120V phase-phase / phase-neutral
Line Current 25A
Coupling Voltage 3300V (100kHz / 1MHz)
Damping as per BS EN61000-4-12
Decoupling as per BS EN61000-4-12
Coupling configuration L1-L2 / L1-L3 / L2-L3 / L1-N / L2-N / L3-N
(L1+L2+L3+N)-PE
For more information on Non-maloperate Testing talk to Cranage EMC & Safety
Enquire Now
List your company on FindTheNeedle.